What Size Generator Do I Need for an RV?
Size an RV generator to the largest air-conditioner start, not to the shore cord. Two numbers govern everything: the SERVICE ceiling (30A = 3,600W, 50A = 12,000W) and the GENERATOR’s running + surge ratings. An adapter never adds capacity. If your rig has a second rooftop AC or needs more than 3,500 running watts, compare the 7,500-watt generator guide and the rooftop camper air-conditioner wiring guide.
⚠️ Generator safety — read first.
Never plug a generator into a wall outlet and never backfeed your house wiring — it can kill line workers and destroy the generator when power returns. To power house circuits, use a transfer switch or inlet box installed by a qualified professional.
Run a portable generator outdoors only, at least 20 feet (6 m) from doors, windows and vents, with the exhaust pointed away from the house (CDC). Never run it in a home, garage, basement or shed — a garage with the door open is NOT safe. Fit battery-operated carbon monoxide alarms in your home, near sleeping areas. Let the engine cool before refuelling, and store fuel outside living areas in labelled containers.
Scope: North America only — 120/240V split-phase, 60 Hz residential and RV systems. This guide does not cover other countries’ voltages or frequencies, or industrial three-phase power.
Answer Table 1 — RV service ceilings
Sources: 30A TT-30 = 120V × 30A; 50A 14-50 = 2 × 120V × 50A. 50A is 3.3× the 30A figure, not 1.7×.
| Service | Plug | Voltage | Max power | Continuous (80%) |
|---|---|---|---|---|
| 30A RV | NEMA TT-30 (3 prongs: hot, neutral, ground) | 120V, one leg | 120 × 30 = 3,600W | 2,880W |
| 50A RV | NEMA 14-50 (4 prongs: 2 hots, neutral, ground) | 120/240V split-phase, two legs | 2 × 120 × 50 = 12,000W (3.3× the 30A figure, not 1.7×) | 9,600W total, 4,800W per leg (6,000W max per leg) |
Answer Table 2 — worked examples (30A vs 50A, shore and boondocking)
R = running total; D = largest single surge delta; P = R + D. Verdicts: YES / NO / CANNOT CONFIRM. Motors start one at a time — starting watts of two motors are never added together.
| # | Situation | R (W) | D (W) | P (W) | Verdict |
|---|---|---|---|---|---|
| RV1 | 30A shore: one 13.5k AC 1,800 + converter 300 (near-full bank) + LED 150 + TV 190 | 2,440 | 1,000 / AC | 3,440 | YES on 30A shore (2,440 ≤ 2,880 continuous; 3,440 ≤ 3,600 service) |
| RV2 | 30A shore: same, converter 800 (flat bank) | 2,940 | 1,000 / AC | 3,940 | CANNOT CONFIRM the start — running fits the 3,600W breaker but exceeds the 2,880W continuous guideline, and the 3,940W start exceeds the service rating. Whether the pedestal breaker holds the half-second start depends on its trip curve. Fix: charge the battery first (converter → 300W), then run the AC (→ RV1). |
| RV3 | 30A shore: AC 1,800 + converter 800 + TV 190 + LED 150 + laptop/phones 300 | 3,240 | 1,000 / AC | 4,240 | CANNOT CONFIRM / effectively NO — same start problem as RV2, worse. Shed loads before the AC starts. |
| RV4 | 30A shore: AC 1,800 + microwave 1,200 (converter off / battery full) | 3,000 | 1,000 / AC | 4,000 | YES if the AC is already running when you start the microwave (no new motor start, 3,000 ≤ 3,600). NO if the AC tries to start while the microwave is on (4,000 > 3,600). Stagger — this is the sequential-start rule in practice. |
| RV5 | 30A shore: AC 1,800 + converter 800 + microwave 1,200 | 3,800 | 1,000 / AC | 4,800 | NO — running total alone exceeds the 3,600W service. |
| RV6 | 30A shore: 15k AC 2,000 alone | 2,000 | 1,300 / AC | 3,300 | YES (2,000 ≤ 2,880; 3,300 ≤ 3,600) |
| RV7 | 30A shore: 15k AC + converter 300 + LED 150 | 2,450 | 1,300 / AC | 3,750 | CANNOT CONFIRM the start (3,750 > 3,600 service). With a soft-start kit on the AC, recheck against the kit’s published starting figure — the page gives no soft-start number (it varies by kit and AC model). |
| RV8 | 30A shore: two 13.5k ACs | 3,600 | 1,000 / AC | 4,600 | NO — running total alone uses the whole service; anything else trips it. |
| RV9 | 50A shore: two 13.5k ACs 3,600 + converter 800 + microwave 1,200 + water heater 1,400 + RV fridge 400 + LED 150 + TV 190 | 7,740 | 1,000 / AC | 8,740 | YES on 50A shore, IF the legs split right. Total 7,740 ≤ 12,000. Per-leg example split: leg A = AC 1,800 + microwave 1,200 = 3,000W; leg B = AC 1,800 + water heater 1,400 + converter 800 + fridge 400 + LED 150 + TV 190 = 4,740W. Both ≤ 6,000W per leg. CANNOT CONFIRM for a rig whose panel puts both ACs and the water heater on one leg — that leg would see 1,800+1,800+1,400 = 5,000W running plus the AC start, and the panel layout is rig-specific. Check your panel. |
| RV10 | Boondocking, 30A rig: generator for AC 1,800 + converter 600 (half-drained bank) + TV 190 + laptop/phones 300 | 2,890 | 1,000 / AC | 3,890 | 3500W class — YES, BARELY (need 2,890 × 1.2 = 3,468 ≤ 3,500 — 32W margin; surge allowance 4,375 ≥ 3,890). Charge the battery before the hottest part of the day, or drop the laptop chargers. With the converter at 800W (flat bank): R 3,090, need 3,708 > 3,500 → next size up — see the 7500W guide. |
| RV11 | Boondocking, 50A coach: two 13.5k ACs + converter 800 + RV fridge 400 + LED 150 + TV 190 | 5,140 | 1,000 / AC | 6,140 | 7500W class (need 5,140 × 1.2 = 6,168; surge allowance 9,375 ≥ 6,140). The dedicated 7500W guide covers this size — this page states the size only. Also: a 120V-only generator CANNOT feed a 50A rig’s second leg; the generator must have a 120/240V outlet. |
How to read this table: R = running watts of everything on at once. D = the single largest starting surge (starting − running) among the motors on the list, counted once — motors start one at a time, so starting watts of two motors are never added together. P = R + D, the momentary draw the generator must survive. Need = R × 1.2 (20% headroom). A size fits only if its running rating ≥ Need and its surge allowance (×1.25 × running rating as a planning assumption) ≥ P. Always check the actual surge rating on your unit’s own spec sheet. Wattage figures: Honda generator wattage estimation guide; Champion generator wattage chart; Generac GP series worksheet. The nameplate on your own appliance always beats this table.
How to size for your RV — 5 steps
- Find your service: 30A (TT-30, one 120V leg, 3,600W) or 50A (14-50, two legs, 12,000W). The plug shape tells you — read Table 1.
- List what runs at the same time on a hot afternoon: the AC(s), the converter (300W near-full, 800W flat bank — check which state your battery is in), microwave, water heater (1,400W electric — or switch it to propane and drop it from the list), fridge, lights, TV.
- Add the running watts, add the single largest AC starting surge once (sequential start), and check the 80% continuous ceiling (2,880W on 30A) as well as the breaker rating.
- On 50A, split the loads by leg: no leg may exceed 6,000W (4,800W continuous). Find your panel layout — both ACs on one leg is the classic trip.
- For a generator (boondocking), apply the method: running × 1.2 ≤ running rating, peak ≤ surge rating. A 30A rig wants ~3,500 running watts; a 50A coach with two ACs wants the 7500W class. Adapters do not add capacity.
Bill of Materials (BOM) — RV Generator Kit
Adapters change the plug, never the capacity — a 50A rig on 30A service still has 3,600W: For a house rather than an RV, the whole-house guide builds the load list the same way.
- 3500W-class inverter generator with TT-30 (30A RV) outlet: For 30A rigs (RV10)[Amazon]
- 30A TT-30 dogbone adapter: Connects a 30A rig to a 30A pedestal or generator outlet[Amazon]
- 50A-to-30A dogbone adapter: Lets a 50A rig plug into 30A service; capacity stays 3,600W[Amazon]
- RV surge protector / EMS (electrical management system): Protects the coach from pedestal faults and low voltage[Amazon]
- Soft-start kit for the rooftop AC: Brand-matched to your AC unit; check compatibility before buying; no starting-watts claim on this page[Amazon]
- Battery-operated carbon monoxide alarm: Fit one near sleeping areas before the first run[Amazon]
Frequently Asked Questions — Generator Size for an RV
What size generator do I need for a 30A RV?
About a 3500W-class generator: one 13.5k BTU AC (1,800W running) + converter at 600W + TV + laptop chargers is 2,890W running, 3,890W at the AC’s start — need 3,468W running, inside the 3500W class by 32W. With a flat battery (converter 800W) it tips over into the next size up, so charge the battery first.
What size generator for a 50A RV with two air conditioners?
The 7500W class: two 13.5k ACs + converter + fridge + lights + TV is 5,140W running, 6,140W at one AC’s start (need 6,168W running). The dedicated 7500W guide covers this size. And the generator must have a 120/240V outlet — a 120V-only unit cannot feed the second leg.
Is 50A service just “a bit more” than 30A?
No — 3,600W vs 12,000W, 3.3 times. 30A is one 120V leg; 50A is two 120V legs (120/240V split-phase). Every appliance in the coach still runs on 120V; the difference is how many legs feed them.
Can I run the microwave while the air conditioner is on?
If the AC is ALREADY running, yes — 1,800 + 1,200 = 3,000W, inside 30A service. If the AC tries to START while the microwave is on, the peak is 4,000W against a 3,600W service — CANNOT CONFIRM it will hold. Start the AC first, then the microwave.
Why does my generator trip when the battery is flat?
The converter/charger is the hidden load: ~300W with a full battery, ~800W with a flat one (55A converter). On a 30A rig that 500W swing is the difference between fitting and tripping. Charge the battery before the hottest part of the day, or switch the water heater to propane (drops 1,400W).