100 Amp 12V Wire Size Chart & Voltage Drop Calculator

Sizing a 100A @ 12V DC circuit (1200 Watts) for 100A LiFePO4 battery BMS interconnects, 1200W 12V inverters, and 100A MPPT charge controllers. Compare 3% critical voltage drop vs. 5% standard drop from 3 ft to 50 ft below.

Pre-Loaded: 100 Amps @ 12V DC (1200W Continuous Load)

Real-time AWG sizing, thermal ampacity verification, SVG wiring diagram & shareable BOM generator

Volts
= 1,200 Watts
Amps
Watts

Tip: Type either Amps or Watts — both sync automatically.

Round-Trip Loop: 20 ft
Feet
Recommended Wire Size
2 AWG
33.6 mm² (6.54mm core) Drop Limited
Actual Voltage Drop
2.65% (-0.32V)
At Load: 11.68V Heat Loss: 31.8W
Required Fuse & Lugs
125A Fuse
MRBF (Terminal Fuse Block) or MEGA / ANL Fuse Lug Stud: 3/8" (M10)
Advertisement • CLS-Protected Slot (amp-wire-100-amp-12v)
Google AdSense / Header Bidding Unit Ready (Zero Layout Shift Container)

100 Amp 12V Wire Gauge Chart by Distance (3% vs. 5% Drop)

Use the 3% Max Drop column for solar MPPT controllers, inverters, DC-DC chargers, and diesel heaters. Use the 5% Max Drop column for general LED lighting or intermittent pumps:

One-Way Distance Round-Trip Loop 3% Critical Drop Wire Actual Drop (3% Col) 5% Standard Drop Wire Recommended Fuse
3 ft One-Way 6 ft Loop 4 AWG 1.26% (-0.15V) 4 AWG 125A
5 ft One-Way 10 ft Loop 4 AWG 2.11% (-0.25V) 4 AWG 125A
10 ft One-Way 20 ft Loop 2 AWG 2.65% (-0.32V) 4 AWG 125A
15 ft One-Way 30 ft Loop 1/0 AWG 2.5% (-0.3V) 2 AWG 125A
20 ft One-Way 40 ft Loop 2/0 AWG 2.65% (-0.32V) 1 AWG 125A
25 ft One-Way 50 ft Loop 3/0 AWG 2.63% (-0.32V) 1/0 AWG 125A
30 ft One-Way 60 ft Loop 4/0 AWG 2.5% (-0.3V) 1/0 AWG 125A
40 ft One-Way 80 ft Loop 2x 2/0 or 4/0 Parallel 3.33% (-0.4V) 3/0 AWG 125A
50 ft One-Way 100 ft Loop 2x 2/0 or 4/0 Parallel 4.17% (-0.5V) 4/0 AWG 125A